8 ISOLATED ANALOG INPUTS CONDITIONER TERMINAL BLOCK
FEATURES  

 

  • 8 protected and isolated 3-port analog inputs
    INPUTS/OUTPUTS/POWER SUPPLY
  • Inputs :
    Voltages, Current loop,
    Thermocouples, PT100, AD590
  • Gains ranging from ± 50mV to ± 10V FS
  • 4th order low-pass filtering
    (CF from 10Hz to 1KHz)
  • Long distance differential outputs
  • Cold weld compensation for thermocouples
    J, K, T, E, R, S, X
  • Conditioning and linearization platinum sensor (PT100)
  • Conditioning AD 590 1µA / °K
  • Single power supply + 24V / 0.5A
  • 4, 5 or 6Te format 300 series form factor

 

 

 

Adas board
 
DESCRIPTION

Developed to meet the requirements of signal conditioning rationally, the BCI 382 terminal block provides a solution for HIGH and LOW level analog input acquisition.

The 3-port type isolation enables ground and common mode problems to be overcome.

The BCI 382 terminal block also provides:

  • cold weld compensation for the thermocouples,
  • conditioning and linearization of the platinum sensors
  • current loop closing,
  • conditioning of AD 590 type silicon sensors.

Equipped with software-programmable gains (B :1, 2, 4, 8 AND D : 1, 10, 100, 1000) and differential analog outputs, the BCI 382 terminal block can be controlled by analogic and digital coupler boards from which it can be separated by up to 30m.

Of painstaking design, it is used to advantage in industrial environments where the cost of conditioning has to be taken into account.

Afaq
9 rue Georges Besse – BP 47 – 78330 FONTENAY LE FLEURY – FRANCE
Tél.:(33) 1 30 58 90 09 - http://www.adas.fr - mail@adas.fr
Afaq
 

 

BCI 382

SPECIFICATIONS (t = 25°C)

TYPE

ISOLATED ANALOG INPUTS

INPUTS

8 isolated differential channels

 

ISO

HMC

- Isolation between channels

1000V

400V

- Isolation between inputs/outputs

1000V (750Vrms)

200V / 1MΩ

- Protection

± 50Vrms

- Common mode rejection

> 80dB

- Gain input

Function version select

- Offset and gain drift

≤ 1µV / °C and ≤ 50ppm / °C

VOLTAGE VERSION

From 50mV FS to ± 10V FS Zin ≥ 2M Ω

CURRENT VERSION

Current loop closing R = 50 Ω

THERMOCOUPLE VERSION

- Types compensated

J, K, T, E, R, S, X

- Cold weld compensation

t° = 25°C : ± 1 °C

- Compensation range

t° = 10°C to 40°C : ± 1. 5°C

- Open loop detection

Yes (+ FS)

PLATINUM SENSOR VERSION

- Assemblies supported

3-wire or 4-wire (RS ≤ Ω)

- Injection current

1mA (PT100) ; 100µ∆ (PT1000)

- Linearization (PT100)

Yes (α1 = 0.00385 or α2 = 0.00390) To specify in order

- Precision min. (G + L)

± 0.2°C (t = 100°C) ; ± 1.5°C (t = 800°C)

AD 590 VERSION

- Temperature range

- 55°C / + 150°C (G = 1) with 1µA / °K

DIFFERENTIAL OUTPUTS

- Type Differential or Single ended (SE)

- Voltage

± 10V FS

- Output impedance

< 50 Ω

- Max. current

5mA (RL = 2K Ω )

 

ISO

HMC

- Precision and linearity

≥± 0.1 % of FS (± 0.03 typical)

≥± 0.03 % of FS (± 0.015 typical)

- Programmable gains

B = 1, 2, 4, 8 (by straps or software via digital board)

  D = 1, 10, 100, 1000

FILTERING

- Type

Butterworth 4th order polynomial low-pass

- Cutoff frequency

According to range (see table) For other versions, consult us for value and price

CONNECTION

- Process

LEMO 5-pin connectors for plugs ref. : FGG1B305CLAD62

- System (plug-in / withdrawable)

DIN 41612 64-pin female for BCI series backplane

POWER SUPPLY

- Voltage / current

+ 24V rated / 0.5A

- Protections

Delayed-action fuse and polarity reversal

PRESENTATION

- Format

Double EUROPE / 4, 5 Te (or 6Te)

- Dimensions in mm (L x W x H)

233,35 x 160 x 25,40 (or 30,48)

- Fitting

In 300 series rack (BCI300-RACK)

ENVIRONMENT

- Operating temperature

- 20°C to + 70°C

- Storage temperature

- 25°C to + 85°C

- Relative humidity

90 % (without condensation)

EUROPEAN NORMS  
  EMC - EN 61326 - EN 55011 Class A
  CE Compliance
  ROHS - 2002/95/EC
HOW TO ORDER?

Refer to next page

ACCESSORIES

19”/6U enclosure to receive
12, 16 or 20 BCIs series 300

BCI300-RACK

   
14
29/52
 
HOW TO ORDER ?
BCI382/YYY-*/+++
  YYY Option : HMC : High common mode ISO : Isolated
  ZZ Option : SE : Unifilar output  
  * Front Panel :( 4 = 4Te 5= 5Te 6 = 6Te ) +++ input type (Voltage/Current, Thermocouple, Platinum Sensor, AD590)
  E.g. : BCI382/ISO-5/VHB/SE  
   

VOLTAGE/COURANT (FS)

VHD
= ± 10V to ± 10mV Fc = 1000Hz

VHB

= ± 10V to ± 1.25V Fc = 1000Hz

VMB

= ± 2V to ± 250mV Fc = 100Hz

VBB

= ± 400mV to ± 50mV Fc = 10Hz

V8B

= ± 40mV to ± 5mV Fc = 10Hz

BBB

= 4/20mA R = 50 Ω Fc = 1000Hz
(- 10V = 4mA / + 10V = 20mA)

BCB

= 20mA R = 50 Ω Fc = 1000Hz
( 20mA → 10V)

BDB

= 4/20mA R = 50 Ω Fc = 1000Hz
(0V = 4mA / 10V = 20mA)

 

GAINS

B

= 1, 2, 4, 8

D

= 1, 10, 100, 1000

The thermocouple ranges are given in positive FS.


Use of the negative values is also possible :
E.g. : Type K = - 6.458mV = - 270°C

 

THERMOCOUPLE
MAXIMUM VALUE OF "t" FOR VS = 10V ACCORDING TO GAIN FC = 10Hz

 

Thermocouple

G = 1

G = 2

G = 4

G = 8

80mV FS

40mV FS

20mV FS

10mV FS

THJ

J

1200°C = 8.692V

714°C

367°C

186°C

THK  

K

1372°C = 6.859V

968°C

485°C

247°C

THT  

T

-

690°C

386°C

214°C

THE  

E

1000°C = 9.544V

537°C

287°C

153°C

THR  

R

-

-

1684°C

962°C

THS  

S

-

-

1768°C = 9.349V

1036°C

THB  

B

-

-

-

1492°C


PLATINUM SENSOR
Range FS ACCORDING TO GAIN FC = 10Hz

 

G = 1

G = 2

G = 4

G = 8

- 50°C / + 800°C

- 50°C / + 400°C

- 50°C / + 200°C

- 50°C / + 100°C

RTC 

100 Ω

RTK  

1000 Ω

 

to 0°C


AD590
Fc = 10Hz

 

G = 1

G = 2

G = 4

G = 8

AD

150°C

75°C

37.5°C

-


 
DOCUMENTATION Revision B - English Version
  Revision A - English Version
 
 
French Version