BCI 184
8 ISOLATED ANALOG INPUTS
FEATURES  
  • 8 conditioned and isolated analog inputs
  • ± 200V common mode voltage
  • CMRR ≥ 86dB (F ≥ 100Hz)
  • EMC/ESD protected and filtered inputs
  • Gains from ± 50mV FS to ± 10V FS
  • 2 nd order filtering (CF to be defined)
  • Single + 5V / 0.5A power supply
  • Cold weld compensation for thermocouples
    J, K, T, E, R, S
  • 3 and 4-wire platinum sensor conditioning and linearization
  • Conditioning AD590 (1mA/°K)
  • 6U /5Te format 100 series form factor

 

Adas board

 
DESCRIPTION

 

Developed to meet the requirements of signal conditioning rationally, the BCI 184 terminal block provides a solution for HIGH and LOW level analog input acquisition.

The high common mode of the BCI 184 enables ground and common mode problems to be overcome.

The BCI 184 terminals blocks also provides cold weld compensation for thermocouples, and platinum sensor conditioning and linearization.

Of painstaking design, it is used to advantage in industrial environments where the cost of conditioning has to be taken into account.

 

Afaq
9 rue Georges Besse – BP 47 – 78330 FONTENAY LE FLEURY – FRANCE
Tél.:(33) 1 30 58 90 09 - http://www.adas.fr - mail@adas.fr
Afaq
 

 

BCI 184

SPECIFICATIONS (t = 25°C)

TYPE

ANALOG CONDITIONING INPUTS

INPUTS TO THE PROCESS

- Number of channels

8

- Voltage version

From 50mV FS to ± 10V FS ; Zin = 1M Ω

- Current version

Current loop closing R = 50 Ω

INPUT PROTECTION

- Level

100Vrms / t < 2s (for V models)

ISOLATION

- Between channels

500V max. / 800KΩ

- Inputs/outputs CMV

± 200V DC (500V max.)

- Commun mode rejection

≥ 86dB (F ≤ 100Hz)

THERMOCOUPLES VERSION

- Type

J, K, T, E, R, S

- Cold weld compensation

t° = 25°C : ± 1 °C

 

t° = 10°C to 40°C : ± 1. 5°C

- Open loop detection

Yes

PLATINUM SENSOR VERSION

- Type

3 and 4 wires

- Input current

1mA

- Linearization (PT 100)

Yes (α 1 = 0.00385 and α 2 = 0.00392)

OUTPUTS TO THE SYSTEM

- Voltage

± 10V FS

- Output impedance

< 10 Ω

- Max. current

5mA

- Global error (gain, offset, linearity)

≤ ± 0.05 % of FS typical (± 0,1 % max)

FILTERING

- Type

Butterworth 2nd order polynomial low-pass

- Cutoff frequency

To be defined when ordering (see table)

- Frequency max.

20KHz

CONNECTION

- Process

Removable screw terminals Ø ≤ 1.5mm ² with 3.81 pitch

- System

HE 10 / 50-pin and mini HE10 / 50-pin

POWER SUPPLY

- Voltage

+ 5V / 0.5A

PRESENTATION

- Format

Double EUROPE 6U / 5Te

- Dimensions in mm (L x W x H)

233. 3 x 120 x 20.48

- Fitting

In 100 series rack or 6U enclosure

ENVIRONMENT

- Operating temperature

- 20 °C to + 70°C

- Storage temperature

- 25 °C to + 85 °C

- Relative humidity

90 % (without condensation)

- Protection

Double Π filter on the power supply

EUROPEAN NORMS  
  EMC - EN 61326 - EN 55011 Class A
  CE Compliance
  ROHS - 2002/95/EC
HOW TO ORDER?

Refer to the next page.

ACCESSORIES

19”/6U enclosure to receive
16 x BCIs series 100

BCI100-RACK

   
12
23/28
 

HOW TO ORDER?   BCI 184 / ** - ++

VOLTAGE
CURRENT
THERMOCOUPLES (°C)
 
PLATINIUM PROBE
 
CUTOFF
    TYPE J  
TYPE K
       
FREQUENCY
VB
= ± 50V
BA
= 0/20mA R = 50Ω J2 = -210/+370 K3 = -210/+250  

A1

= - 50/+ /100°C   F0 = 5Hz
 
(0mA = -10V/20mA = +10V) J1 = -210/+705 K2 = -210/+484  

 

   
VA
= ± 20V
BB
= 4/20mA R = 50Ω J0 = -210/+1200 K1 = -210/+964  

B1

= - 50/+ /250°C   F1 = 10Hz
 
(4mA = -10V/20mA = +10V)     K0 = -210/+1372  

 

   
V0
= ± 10V
BC
= ± 20mA R = 50Ω          

C1

= - 50/+400°C   F2 = 50Hz
 
( ± 20mA Þ 10V)  
TYPE T
 

TYPE E

 

 

   
V1
= ± 5V
BD
= 4/20mA R = 50Ω  

 

D1

= - 50/+800°C

F3 = 100Hz
 
(4mA = 0V/ 0mA = 10V) T1 = -270/+250 E2

= -270/+290

 

 

 

 
V2
= ± 2V
BE
0 Þ 40mA T0 = -270/+390 E1

= -270/+535

 

L1

= - 50/+50°C

F4 = 500Hz
 
(0mA = -10V ; 40mA = +10V) E0

= -270/+1000

  Eg. : BCI184/B1/F1

V3
= ± 1V
BF
= ± 10mA

     

F5 = 1KHz
 
( ± 10mA Þ ± 10V)
TYPE R

TYPE S

     

V4
= ± 500mV
BG
0 Þ 50mA

 
AD 590

F6 = 2KHz
 
(0mA = -10V ; 50mA = +10V) R1 = - 270 / + 960 S1

= -270/+1030

     

V5
= ± 200mV Eg. : BCI184/BC/F5 R0 = - 270 / + 1650 S0 = -270/+1768   AD = 150°C

F7 = 5KHz
          Eg. : BCI184/E2/F1        
V6
= ± 100mV                   F8 = 10KHz
          The above thermocouple ranges are given in positive FS values.        
V7
= ± 50mV         It is also possible to use negative values :         F9 = 20KHz
          Eg : Type K = - 6,458mV = - 210°C        
V8
= ± 20mV                        
Eg. : BCI184/V4/F2      

     


 

 

 
DOCUMENTATION English Version
 
 
 
French Version