BCI 140
16 ISOLATED AC/DC DIGITAL INPUTS
FEATURES  
  • 16 photocoupled digital inputs
  • Versions : 5V DC, 12V, 24V, 48V, 96V,192V AC/DC
  • Precise triggering threshold
  • Filtering for noise immunity
  • Terminals or LEMO plug connectors
  • FRONT panel display LEDs
  • Direct interface with ADAS I/O boards
  • 6U / 5Te format 100 series form factor

 

Adas board
 
DESCRIPTION

Developed in the context of industrial interfaces for digital I/O boards, the BCI 140 terminal block conditions 16 photocoupled inputs.

The channels are isolated from one another and from the system (≥ 1000V)

Each channel has:

  • filtering for high noise immunity
  • a precise triggering threshold
  • a wide safety zone against voltage surges
  • a switching display led

The presence of two commons per group of 8 channels avoids having to wire the “returns” in industrial installations.

Of compact and well-designed presentation (6U/5Te), the BCI 140 terminal block can be easily integrated into a BCI100-RACK 19 inches enclosure able to receive 16 terminal blocks to achieve a total of 256 I/O. The user has choice between terminals 3.81 pitch or LEMO plug 2 poles for the connectors.

 

Afaq
9 rue Georges Besse – BP 47 – 78330 FONTENAY LE FLEURY – FRANCE
Tél.:(33) 1 30 58 90 09 - http://www.adas.fr - mail@adas.fr
Afaq
 

 

BCI 140

SPECIFICATIONS (t = 25°C)

TYPE

PHOTOCOUPLED INPUTS

INPUTS

- Number of channels

16 photocoupled

- Isolation between channels

≥ 1000V AC/DC

- I/O isolation

≥ 1000V AC/DC

- Versions

A

B C D E F

- Rated voltage

5V 12V 24V 48V 96V 192V

- Minimum threshold

2,6V 10V 19V 36V 76V 100V

- Maximum voltage

10V 24V 48V 96V 160V 260V

- Current at Vrated (nominal input)

2mA 12mA 12mA 12mA 12mA 5mA

- Setting time

≈ 2 to 3ms at Vrated t (ON) at Vnominal

- Release time

≈ 2 to 3ms at Vrated t (OFF) at Vnominal

- Photocoupler

HCPL 2300. |__________________HCPL 3700__________________|

- Commons

1 per group of 8 channels

OUTPUTS TO THE SYSTEM

- Level

Active Low Level or Active High Level (INV)

- Compatibility

TTL ABT 541 or ABT 540 (INV)

- Display

1 led per channel

PRESENTATION

- Format

Double EUROPE 6U / 5Te

- Dimensions in mm (H x W x D)

233.35 x 100 x 25,40

- Fitting

In 100 series rack or 6U enclosure

- Connection to process

Phoenix 3-pin / 3.81 pitch plug-in

 

Option : LEMO plug 2 poles

- I/O board link

HE10 / 50-pin and mini HE10 / 50-pin

- 32-channel extension link

HE10 / 50-pin

POWER SUPPLY

 

  5V / 40 0mA max.

ENVIRONMENT

- Operating temperature

- 20 °C to + 70°C

- Storage temperature

- 25 °C to + 85 °C

- Relative humidity

90 % (without condensation)

EUROPEAN NORMS
EMC - EN 61326 - EN 55011 Class A
CE Compliance
ROHS - 2002/95/EC
HOW TO ORDER?

BCI 140 / **

**

VOLTAGE

A =
B =
C =

D =

E =
F =

5V
12V
24V
48V
96V
192V

E.g. : BCI 140/D V IN = 48V AC/DC


Option LEMO plug

For Active High Level

19”/6U enclosure to receive
16 x BCIs series 100

BCI 140/*/L E.g. : BCI 140/D/L

BCI 140/*/INV (E.g. : BCI 140/D/INV ; BCI 140/D/L/INV )

BCI100-RACK

   
14
23/02
 
 
DOCUMENTATION English Version
 
 
 
French Version